The CAN to 1 Signal Output Controller features 2 signal outputs configurable as: 0-5V; 0-10V; 0-20 mA; 4-20 mA; or PWM signal. Networking is via 1 CAN SAE J1939 port. It is operational from 9 to 36 Vdc (12 or 24 Vdc). The controller is designed for EMC compliance for power genset control applications. Configuration is with the Axiomatic Electronic Assistant.
Items |
/ImgCustom/20/placeholder_notavailable.gif AX130760 CAN to 1 Signal Output Controller, SAE J1939 |
/Asset/AX130760.jpg AX130761 CAN to 1 Signal Output Controller, CANopen® |
||
Description |
N/A
CAN to 1 Signal Output Controller accepts power supply voltages from 9 to 36 VDC. Versatile control algorithms/ function blocks allow the user to configure the controller for a wide range of applications without the need for custom firmware. All logical function blocks on the unit are inherently independent from one another but can be configured to interact with each other. All parameters are configurable using Axiomatic Electronic Assistant. The hardware design allows for the controller to have a wide range of output types: Current, Voltage, and PWM. It can operate at standard 250 kbit/s and 500 kbit/s and non-standard 667 kbit/s and 1 Mbit/s baud rates. The required baud rate is detected automatically upon connection to J1939 CAN network. |
N/A
CAN to 1 Signal Output Controller accepts power supply voltages from 9 to 36 VDC. Versatile control algorithms/function blocks allow the user to configure the controller for a wide range of applications without the need for custom firmware. All logical fuction blocks on the unit are inherently independent from one another but can be configured to interact with each other. The hardware design allows for the controller to have a wide range of output types: Current, Voltage, and PWM. It ca noperate at baud-rates of 10 kbit/s, 20kbit/s, 50kbit/s, 125kbit/s, 250kbit/s, 500kbit/s, 800kbit/s, and 1Mbit/s. |
||
Technical Specifications | N/A CAN to 1 Signal Output Controller | |||
Order Code | N/A P/N: AX130760 | N/A P/N: AX130761 | ||
Operating Voltage | N/A 12 or 24Vdc Nominal (9…36Vdc) The minimum allowable supply voltage for the power pin is 8 VDC. | |||
Signal Outputs |
N/A
1 signal outputs configurable as: 0-5V 0-10V 0 - 20 mA 4 - 20 mA Frequency or PWM Signal |
|||
Relay Output | N/A | |||
Communications | N/A 1 CAN (SAE J1939) | N/A 1 CAN (CANopen® ) | ||
CAN Baud Rate | N/A | |||
Control Logic | N/A Axiomatic Electronic Assistant AX070502, or AX070506K Pre-programmed with standard logic. | N/A Pre-programmed with standard logic | ||
Enclosure |
N/A
Plastic Enclosure, integral connector Nylon 6/6, 30% Glass Laser Welded 3.02 x 2.41 x 1.26 inches (77 x 61.3 x 32 mm) L x W x H including integral connector |
|||
Connections | N/A Integral TE Deutsch equivalent 6 pin receptacle (P/N: DT04-6P). | |||
Protection Rating | N/A IP67 | |||
Operating Temperature | N/A -40 to 85 ºC-40 to 185 ºF | |||
Applications |
N/A
Distributed controls in
|
N/A
Distributed controls in
|
||
Fieldbus | N/A SAE J1939 | N/A CANopen® | ||
Marks | N/A | |||
Accessories |
N/A
AX070119, Mating Plug Kit (1 DT06-6S, 1 W6S, 6 0462-201-16141) AX070502, Electronic Assistant KIT (AX070501 USB-CAN, 2 Cables, Installation Instructions) |
N/A
AX070119, Mating Plug Kit (1 DT06-6S, 1 W6S, 6 0462-201-16141) |
||
User Configurability | N/A | N/A EDS File | ||
|