The 20 PT1000 RTD Scanner monitors 20 2-wire PT1000 inputs from a diesel engine and the temperature information is provided to the engine control system over a SAE J1939 CAN bus. Temperature information can include exhaust temperature, winding temperature, and fluid temperature. All channels of temperature data are automatically sent over the CAN bus when power is applied with no additional programming or configuration required. The RTD Scanner is designed to meet the environmental, EMC and vibration requirements of vehicle and power generator set applications.
Unit of Measure
Technical Specifications |
N/A
Twenty (20) 2-wire PT1000 Inputs CAN, SAE J1939 |
Order Code |
N/A P/N: AX184200 |
Operating Voltage |
N/A 12V, 24V or 48Vdc Nominal (8 to 65 VDC Power Supply Range) |
Reverse Polarity Protection |
N/A Provided |
RTD Inputs |
N/A 20 Inputs 200 - 4000 Ohms (Suitable for PT1000) |
Enclosure |
N/A
Rugged Aluminum Housing, Stainless Steel End Plates, Neoprene Gaskets 142.88 x 149.00 x 73.00 mm 5.63 x 5.86 x 2.87 inches (L x W x H) |
Protection Rating |
N/A IP67 |
Operating Temperature |
N/A -40 to 185 ºF-40 to 85 ºC |
CAN |
N/A SAE J1939 |
Datasheet |
N/A
TDAX184200 |
User Manual |
N/A
AX184200 User Manual |
STEP Files (3D) |
N/A
Generic TC-RTD-AIO |
Compliance |
N/A
LVD - DoC - All RoHS - DoC - All |
Accessories |
N/A
AX070502, Axiomatic Electronic Assistant KIT (USB-CAN Converter, USB-A to USB-B Cable, CAN Cable, Installation Instructions) |