The Current Converter accepts a 24Vdc power supply (nominal) and a 4-20mA input signal converting it to a current output. Various outputs are available, including 0-200 mA, 20-200 mA, 5-195 mA, 0-100 mA, 20-160 mA, 40- 160 mA, 0-160 mA or 0-50 mA. Span and zero is user adjustable. A diagnostic LED indicates operational status, glowing green when the load, input signal and power supply are connected. The load should be floating, isolated from ground. The circuit board is conformal coated and the unit is available in a 35 mm DIN rail mount housing.
Unit of Measure
Order Code |
N/A P/N: IC-DR-14 (0-50 mA output) |
Operating Voltage |
N/A 24 VDC Nominal (9-45VDC Operating Range) |
Protection |
N/A Reverse Polarity Protection is Provided Transient Protection is Provided |
Current Input |
N/A 4 - 20 mA |
Input Impedance |
N/A 50 Ohms +/- 1 % |
Response Time Output |
N/A <5 mSec. |
Output Current |
N/A
Factory Settings +/- 2mA : 0-50 mA (Other current output ranges are available on request.) Connect output to Output positive terminal and not to GND. |
Output Impedance |
N/A >40 MOhm |
Adjustments |
N/A
Multi-turn Trim Pots (10 Turns) Zero: CW = Increasing Apply 4mA input current and adjust the Zero trimpot to desired minimum output current. Span: CW = increasing Apply 20mA input current and adjust the Span trimpot to desired maximum current output. |
Enclosure |
N/A
DR12, Polycarbonate DIN rail mount (75 x 98.5 x 22.5 mm or 2.95 x 3.88 x 0.89 inches) for high profile DIN rail (35 mm) |
Connections |
N/A #12 to #22 AWG Screw Terminals. |
Protection Rating |
N/A IP40 Rated Housing, Terminals Rated at IP20 PCB is conformal coated. |
Operating Temperature |
N/A 0 to 95% Relative Humidity -40 to 85 ºC-40 to 185 ºF |
Applications |
N/A Industrial Controls Mobile Equipment |
Datasheet |
N/A
IC-DR-XX Datasheet |
Compliance |
N/A
EMC ICDR11 Family LVD - DoC - All RoHS - DoC - All |