The Current Converter accepts a 24Vdc power supply (nominal) and a 4-20mA input signal converting it to a current output. Various outputs are available, including 0-200 mA, 20-200 mA, 5-195 mA, 0-100 mA, 20-160 mA, 40- 160 mA, 0-160 mA or 0-50 mA. Span and zero is user adjustable. A diagnostic LED indicates operational status, glowing green when the load, input signal and power supply are connected. The load should be floating, isolated from ground. The circuit board is conformal coated and the unit is available in a 35 mm DIN rail mount housing.
Unit of Measure

Order Code

N/A P/N: AX130300

Operating Voltage

N/A 24 VDC Nominal (9-45VDC Operating Range)

Enclosure

N/A DR12, Polycarbonate
DIN Rail Mount (75 x 98.5 x 22.5 mm or 2.95 x 3.88 x 0.89 inches) for high profile DIN rail (35 mm)

Protection Rating

N/A IP40 Rated Housing, Terminals Rated at IP20 PCB is conformal coated.

Operating Temperature

N/A 0 to 95% Relative Humidity -40 to 85 ºC-40 to 185 ºF

Applications

N/A Industrial Controls Mobile Equipment

Current Input

N/A 4 - 20 mA

Input Impedance

N/A 50 Ohms +/- 1 %

Response Time Output

N/A <5 mSec.

Output Current

N/A Factory Settings +/- 2mA : 5-195 mA
(Other current output ranges are available on request.)
Connect output to Output positive terminal and not to GND.

Output Impedance

N/A >40 MOhm

Adjustments

N/A Multi-turn Trim Pots (10 Turns)

Zero
CW = Increasing
Apply 4mA input current and adjust the Zero trimpot to desired minimum output current.
Span
CW = increasing
Apply 20mA input current and adjust the Span trimpot to desired maximum current output.

Connections

N/A #12 to #22 AWG Screw Terminals.

Protection

N/A Reverse Polarity Protection is Provided Transient Protection is Provided

Datasheet

N/A IC-DR-XX Datasheet

Compliance

N/A LVD - DoC - All
RoHS - DoC - All