Print Back

The Temperature Scanner monitors up to 20 thermocouples and 2 RTD’s to provide the temperature information to the engine control system over SAE J1939 CAN bus. The channels are independently configurable as Type J, K, B, E, N, R, S or T thermocouples. Temperature information can include exhaust temperature, winding temperature, and fluid temperature monitoring. All 20 channels of temperature data are automatically sent over the CAN bus when power is applied with no additional programming or configuration required. There are 4 universal signal command inputs. The control sets 6 Form C relay outputs. Integral diagnostics determine thermocouple integrity. All inputs are fully isolated from the CAN lines, and from the power supply. The two CAN channels are fully isolated from one another in the hardware which allows for different CAN networks to be connected. In the software, each will also act independently where incoming or outgoing messages can be configured to receive or send on a specific CAN channel. Modbus TCP/IP communications are also available. The scanner is enclosed in a rugged IP67 rated enclosure with an 86 pin TE Deutsch connector.

Unit of Measure

Specifications

Technical Specifications

N/A 20 TC, 2 RTD, 4 Signal Inputs, 6 Relay Outputs Controller, 2 SAE J1939, Ethernet

Order Code

N/A AX180800

Operating Voltage

N/A 12V or 24 VDC nominal (9...60 VDC power supply range)

Protection

N/A Reverse polarity protection is provided
Power supply input section protects against transient surges and short circuits
Open circuit detection
Over or under temperature detection
High temperature shutdown detection

Thermocouple Inputs

N/A Reads 20 TC inputs
Configurable as Type J, K, B, E, N, R, S, T

RTD Inputs

N/A 2 RTD with range of 20 - 400 Ohms

Signal Inputs

N/A 4 Universal Signal Inputs to configurable as voltage, current. frequency, PWM, or digital

Outputs

N/A 6 Form C Relay Outputs

CAN Baud Rate

N/A 2 SAE J1939; Auto

Enclosure

N/A Rugged aluminum housing, anodized, gasket
Connector: 86-pin TE Deutsch DRCP25-86PAA-G005

Isolation

N/A Digital isolation is 400VDC from input to ground
Three-way isolation is provided for the CAN line, inputs and power supply

Product Documents

Datasheet

N/A AX180800 Datasheet

User Manual

N/A AX180800 User Manual
Modbus Address Map AX180800

STEP Files (3D)

N/A AX180800

Compliance

N/A LVD - DoC - All
RoHS - DoC - All

Accessories

Accessories

N/A AX070164, Mating Plug Kit
AX070502, Axiomatic Electronic Assistant KIT (USB-CAN Converter, USB-A to USB-B Cable, CAN Cable, Installation Instructions)