Order Code |
N/A P/N: IC-DR-20 (0-100 mA output) |
Operating Voltage |
N/A 24 VDC Nominal (9-45VDC Operating Range) |
Protection |
N/A Reverse Polarity Protection is Provided Transient Protection is Provided |
Current Input |
N/A 4 - 20 mA |
Input Impedance |
N/A 50 Ohms +/- 1 % |
Response Time Output |
N/A <5 mSec. |
Output Current |
N/A
Factory Settings +/- 2mA : 0-100 mA (Other current output ranges are available on request.) Connect output to Output positive terminal and not to GND. |
Output Impedance |
N/A >40 MOhm |
Adjustments |
N/A
Multi-turn Trim Pots (10 Turns) Zero: CW = Increasing Apply 4mA input current and adjust the Zero trimpot to desired minimum output current. Span: CW = increasing Apply 20mA input current and adjust the Span trimpot to desired maximum current output. |
Enclosure |
N/A
DR12, Polycarbonate DIN Rail Mount (75 x 98.5 x 22.5 mm or 2.95 x 3.88 x 0.89 inches) for high profile DIN rail (35 mm) |
Connections |
N/A #12 to #22 AWG Screw Terminals. |
Protection Rating |
N/A IP40 Rated Housing, Terminals Rated at IP20 PCB is conformal coated. |
Operating Temperature |
N/A 0 to 95% Relative Humidity -40 to 85 ºC-40 to 185 ºF |
Applications |
N/A Industrial Controls Mobile Equipment |
Datasheet |
N/A
IC-DR-XX Datasheet |
Compliance |
N/A
EMC ICDR11 Family LVD - DoC - All RoHS - DoC - All |