Order Code |
N/A P/N: AX031200 |
Operating Voltage |
N/A
12 VDC or 24 VDC nominal (9…60 VDC Power Supply Range) Shutdown Voltage is 7.5 VDC |
Communications |
N/A 2 Isolated CAN ports (SAE J1939), 250 kbps |
Control Logic |
N/A
Standard embedded software is provided. (Application-specific control logic or factory programmed set point file on request) User programmable functionality using Electronic Assistant. |
Enclosure |
N/A
High Temperature Nylon Housing, TE Deutsch P/N: EEC-5X650B 5.67 x 7.92 x 2.15 inches (144.0 x 201.3 x 54.6 mm) L x W x H including integral connector |
Protection Rating |
N/A IP67 |
Operating Temperature |
N/A -40 to 85 ºC-40 to 185 ºF |
Outputs |
N/A
9 Outputs: 4 Isolated Analog Outputs (user selectable as 0-5V or 0-10V Voltage; or 4-20 mA, 0-20 mA Current) 4 Relay Outputs (2A@ 250V NO) 1 Output (2A) to drive a proportional or ON/OFF hydraulic valve |
Applications |
N/A
Power Gen Set Engine Control Systems Off-highway Machine Automation Oil and Gas Equipment Automation |
Inputs |
N/A
11 Inputs, user selectable from the following: 4 Isolated Analog Inputs, 2 Isolated Digital Inputs, 1 Magnetic Pick Up Input, 4 Universal Inputs Inputs and Power are isolated from the outputs and CAN. |
Enclosure (Filter) |
N/A Box |
Datasheet |
N/A
AX031200 Datasheet |
User Manual |
N/A
AX031200 User Manual |
STEP Files (3D) |
N/A
FG-AX031200 |
Compliance |
N/A
LVD - DoC - All RoHS - DoC - All |