The 2 Bipolar, 8 Universal Signal Inputs Controller operates with Modbus TCP/IP and a SAE J1939 CAN port with auto-baud-rate detection. It has two reference voltages (+5), and two LED indicators. The controller is configurable via the Axiomatic Electronic Assistant.
Unit of Measure
Order Code |
N/A P/N: AX032100 (2 Bipolar A/D and 8 Universal Signal Inputs Controller, Ethernet port (Modus TCP/IP), SAE J1939, auto-baud-rate detection) |
Operating Voltage |
N/A 12 Vdc or 24 Vdc Nominal (8…36 Vdc power supply range) |
Enclosure |
N/A
Phoenix Contact: ME MAX 22,5 G 2-2 KMGY – 2713638 Polyamide, UL94V0, cULus recognized, China RoHS DIN rail TH 35-7.5 114.5 x 22.5 x 99 x 107 mm 4.508 x 0.89 x 3.898 x 4.213 inches (L x H x W x D) |
Connections |
N/A 4 sets of 5 Phoenix Contact MC 1,5/ 5-ST-3,5 GY7035 3.5 mm screw terminal connectors. Accepts 28-16 AWG wire. RJ-45 for Ethernet connection. |
Protection Rating |
N/A IP20 |
Operating Temperature |
N/A -40 to 85 ºC-40 to 185 ºF |
Applications |
N/A
Industrial Control Panels Power Gen Set Engine Control Systems Oil and Gas Equipment Automation Machine Automation |
Inputs |
N/A
2 Bipolar Analog or Digital Signal Inputs: User programmable as Bipolar or Unipolar Voltage, Current, PWM or Digital signal inputs types. Eight (8) universal signal inputs are selectable as bipolar voltage, current, resistive, digital, PWM or frequency signal types: 0-5V, 0-10V 4-20mA, 0-20mA Resistive PWM Frequency Digital |
CAN |
N/A 1 CAN port (SAE J1939) Baud rate: 250, 500, 667 kbit/s, 1 Mbit/s. Auto-Baud Rate Detection Full support for SAE J1939 ECU User-configurable PGN’s |
Ethernet |
N/A Ethernet port (Modus TCP/IP) |
User Interface |
N/A Electronic Assistant, P/N: AX070502 |
Enclosure (Filter) |
N/A DIN Rail |
Datasheet |
N/A
AX032100 Datasheet |
User Manual |
N/A
AX032100 User Manual |
2D Drawing |
N/A
AX032100-MD-A |
Compliance |
N/A
LVD - DoC - All RoHS - DoC - All |
Accessories |
N/A
AX070502, Electronic Assistant KIT (AX070501 USB-CAN, 2 Cables, Installation Instructions) |